Backup Generator Sizing Calculator
What size generator do I need? Running load plus the starting surge of the biggest motor — the step almost every free calculator leaves out, and the reason so many generators stall the first time the pump kicks in.
What are you backing up?
Advanced / Custom Input — the site
The loads
Tick “motor” for anything with a compressor, pump or fan — those are the ones that surge on start. Tick “essential” for what you would keep if you bought a smaller set.
Advanced / Custom Input — the load list
How the biggest motor starts
Advanced / Custom Input — motor starting
Fuel
Advanced / Custom Input — fuel and runtime
Result
List your loads, then press “Work out my generator”.
Estimate only — verify with a licensed electrician/engineer and the manufacturer’s own sizing software before ordering. Transient voltage dip depends on the specific alternator.
Backup Generator Sizing Calculator: Real Motor Starting Surge, Not a Flat 3x Multiplier
Nearly every free generator sizing calculator adds up running watts, applies a flat 3x multiplier for “starting watts,” and stops there, and that flat multiplier is neither the real NEMA method nor conservative enough for the small motors that actually carry the highest code letters. This standby generator calculator works properly instead, as a genuine motor starting kVA calculator it reads the NEMA code letter right off the motor nameplate, or picks a sensible typical one by horsepower if you don’t have it and calculates locked-rotor starting kVA from that letter directly, exactly the method a real generator specification actually uses. It applies that surge to only the single largest motor on top of everything else already running, since motors don’t all start together, shows kW and kVA side by side because gensets are sold in kVA almost everywhere outside North America and offers a second, smaller size for essential loads only, so you can see exactly what backing up just the fridge, the sump pump and some lights actually costs against the whole house. A starter-type comparison shows what a soft starter or VFD on your biggest motor would save, often a whole generator size cheaper than buying the bigger machine.
How to Use
Step 1: Set up your site
- Select Home or small commercial?, this changes the starting-load list you’ll see next.
- Enter your Supply voltage, filled in from your country but editable.
- Open Advanced / Custom Input to set your Power factor (almost every three-phase genset is rated in kVA at 0.8, so a tool that only talks in watts can’t be matched to what’s actually for sale), your Spare capacity to leave for loads added later, and the generator’s Short-term surge capability, a typical set delivers close to twice it’s continuous rating at the 0.4 power factor a starting motor draws, for the second or two the motor needs, so matching the plain 0.8 PF rating straight to locked-rotor kVA is about twice as conservative as it needs to be.
Step 2: Build your load list
- Review the loads already listed, tick motor for anything with a compressor, pump or fan, those are the ones that actually surge on start, and tick essential for whatever you’d keep running if you bought a smaller set instead.
- Tap Add a load for anything not already listed.
- Open Advanced / Custom Input to load a typical starting list instead, essentials only, whole house with air conditioning, a rural house with a well pump, a small shop or a workshop with a compressor, as a worked starting point you can then edit or set How much runs at once, applied to non-essential loads only, 100% is the worst case.
Step 3: Describe how the biggest motor starts
- Select Does it have a starter?, direct-on-line draws about six times full-load current, a soft starter brings that down to two or three times and a VFD to little more than plain running current, on a motor-heavy site this single choice can decide the whole generator size.
- Select the Motor code letter straight off the nameplate, or leave it on Auto to have it picked by size.
- Open Advanced / Custom Input to set Motor efficiency, the Power factor while starting (motors start at a genuinely poor power factor, typically 0.3 to 0.5), your own locked-rotor kVA per hp if you have a manufacturer figure that overrides the code letter or the Voltage dip you can accept, most specifications limit this to 15 or 20 percent.
Step 4: Add fuel details, if you want a running-cost figure
- Select Which fuel? and check the Fuel price, filled in for your country but always editable.
- Enter Hours you expect to run it per outage, for the running-cost figure.
- Open Advanced / Custom Input to set your Typical load while running (consumption is roughly proportional to this), your Tank size (mains gas needs no tank) and Consumption per kWh produced, filled in from the fuel type.
Step 5: Calculate and read your result
- Tap Size the generator. You’ll see the total running load, the starting surge from your single largest motor, the combined required size in both kW and kVA, rounded up to a real commercially available rating, a second, smaller size for essential loads only, what a different starter type on your biggest motor would save and a fuel runtime and running-cost estimate.
Step 6: Export
- Use Copy, Print / PDF or Share link to save or send your result.
Key Features
- Motor starting surge from the actual NEMA code letter, not a flat multiplier. Most free tools apply a fixed 3x to running watts and call it starting watts, but real starting current genuinely varies by motor design, code letter A draws the least at locked rotor, code letter R the most and small motors typically carry the highest code letters of all. This tool reads the letter directly, or defaults sensibly by horsepower when it’s missing and calculates starting kVA from the actual locked-rotor kVA-per-horsepower figure that letter represents.
- The surge is applied to only the single largest motor, never summed across every motor. Motors don’t all start at the exact same instant in a real site, so this tool correctly models the worst realistic case, the biggest motor starting cold while every other simultaneous load is already running steadily, rather than the unrealistic and badly oversized scenario of every motor surging together.
- kW and kVA shown together, because that’s genuinely how gensets are sold. Nearly everywhere outside North America, standby and industrial generator sets are rated in kVA at a nominal 0.8 power factor, so a calculator that only speaks in watts simply can’t be matched to a real manufacturer nameplate. This tool converts and displays both figures together throughout.
- A genuine essential-loads-only alternative, not an afterthought. Tick which of your loads you’d actually keep if you bought a smaller unit, and the tool calculates a second, smaller required size built purely from those essential loads, letting you directly compare the cost of backing up everything against backing up just what actually matters during an outage.
- Starter type modelled as a real, first-class lever on the final size. Direct-on-line starting draws roughly six times full-load current, a soft starter brings that down to two or three times, and a VFD to barely more than the plain running current, and swapping starter type on your single largest motor is very often a meaningfully cheaper fix than buying a bigger generator outright. This tool shows exactly what that swap would save on your specific site.
- Rounds up to a real, commercially available size, not an unbuildable decimal. Rather than reporting something like “17.3 kW” that no manufacturer actually sells, the tool rounds the calculated requirement up to the next standard commercially available rating, so the number you get is one you could genuinely go and order.
- Verified against a published worked industry example, term for term. A 150hp NEMA F motor at 91% efficiency and 0.91 running power factor is reproduced exactly, 795 kVA starting, 123.0 kW running, 135.1 kVA running, and 956 amps at 480V three-phase, matching the published figure of 5.9 times full-load current.
Formula / Logic Used
Running Load for a Motor
Starting Load from the NEMA Code Letter
Where k is the locked-rotor kVA per horsepower that corresponds to the motor’s NEMA code letter, taken from NEC Table 430.7(B), a code letter F gives roughly 5.3 kVA/hp and a code letter K gives roughly 9.0 kVA/hp.
Required Generator Size (Worst Case)
Starter Multiplier Effect on Starting Current
Where is roughly 6 for direct-on-line, 2 for star-delta, 2 to 3 for a soft starter and 1 to 1.5 for a VFD and an autotransformer at a 65% tap reduces starting kVA by the square of that voltage ratio, roughly 0.42 times.
Generator Short-Term Surge Capability
Where is typically around 2, since a genset can normally deliver close to twice it’s continuous rated kVA at the 0.4 power factor of a starting motor, for the second or two the motor actually needs.
Who Should Use This Tool
Homeowners and electricians sizing a standby generator for a house or small commercial site with real motor loads, well pumps, air conditioners, workshop compressors, where a flat “3x starting watts” estimate would genuinely undersize the unit. Also useful for anyone comparing the cost of a full-house generator against an essential-loads-only alternative or checking what a soft starter would save on the biggest motor before specifying a bigger machine.
Frequently Asked Questions (FAQs)
Because a motor draws several times it’s running current for a second or two while it’s rotor is still locked and building up speed and a generator sized only on running watts has no margin left for that surge. This tool calculates that starting surge properly from the motor’s actual NEMA code letter, then sizes the generator to cover it on top of everything else already running.
It’s a letter on the motor nameplate, A through V, indicating locked-rotor kVA per horsepower, and it genuinely varies by motor design, smaller motors often carry a higher code letter and therefore a proportionally bigger relative surge than a flat 3x estimate would suggest. This tool reads the actual letter, or picks a sensible typical one by horsepower size if it’s missing, rather than applying one multiplier to every motor regardless of it’s real starting characteristic.
Because in a real site motors don’t all start at exactly the same instant, the realistic worst case is the single largest motor starting cold while every other load is already running steadily. Summing every motor’s starting surge together would produce a wildly oversized, unrealistic and needlessly expensive generator recommendation.
Standby and industrial generator sets are commonly rated in kVA at a nominal 0.8 power factor almost everywhere outside North America, while smaller portable units are often quoted in kW. This tool calculates and displays both figures together so the result can be matched directly to whatever a real manufacturer’s nameplate actually shows in your market.
Often by a full generator size, since direct-on-line starting draws roughly six times full-load current, a soft starter brings that down to two or three times and a VFD to barely more than the running current itself. This tool lets you switch starter type on your largest motor and see directly how much smaller a generator that change would allow, which is very often meaningfully cheaper than buying a bigger machine outright.