Control Valve Cv Sizing Calculator

Control Valve Cv Sizing Calculator

Liquid · Gas · Steam · choked flow · valve opening

Liquid Service

Gas Service

Pressures are absolute (psia = psig + ~14.7). Temperature in Rankine = °F + 460.

Steam Service (saturated)

Simplified saturated-steam sizing. Pressures are absolute (psia).

Valve Opening (optional)

Enter the valve's rated Cv to estimate what opening % the required Cv corresponds to. Leave blank to skip.

Result

Choose your fluid type and enter the process conditions to get the required Cv using the correct formula for that fluid, a choked-flow check for gas and steam, a suggested standard valve size and the estimated valve opening percentage

These use simplified, widely-taught sizing equations — liquid Cv = Q·√(SG/ΔP), and standard compressible-flow forms for gas and saturated steam — and are intended for preliminary sizing and study. The choked-flow check uses a simplified critical pressure-drop ratio near 0.5; real valves have a manufacturer-specific pressure-recovery factor that shifts this point, and liquids can flash or cavitate before it. Suggested valve sizes come from typical Cv ranges, not any specific product, and a good rule of thumb is that the required Cv should fall around 60–80% of the valve's rated Cv so the valve controls in a stable part of its travel. Always confirm the final selection against the manufacturer's actual Cv and characteristic data, including their FL, xT and viscosity corrections.